๐Ÿ” CVE Alert

CVE-2026-59693

MEDIUM 4.3
CVSS Score
4.3
EPSS Score
0.0%
EPSS Percentile
0th

A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.233.16-7862), Desigo PXC3 (All versions < V01.21.233.16-7862), Desigo PXC4 (All versions < V02.21.194.36-2715), Desigo PXC5.E003 (All versions < V02.21.194.36-2715), Desigo PXC5.E24 (All versions < V02.21.194.36-2715), Desigo PXC7 (All versions < V02.21.194.36-2715). The affected devices are vulnerable to a denial-of-service (DoS) vulnerability. An attacker can exploit this issue by sending a malformed BACnet packet, causing the device to stop responding to BACnet queries. Recovery requires a device reset or reboot to restore normal functionality.

CWE CWE-754
Vendor siemens
Product desigo dxr2
Ecosystems
Industries
IndustrialManufacturing
Published Aug 11, 2026
Stay Ahead of the Next One

Get instant alerts for siemens desigo dxr2

Be the first to know when new medium vulnerabilities affecting siemens desigo dxr2 are published โ€” delivered to Slack, Telegram or Discord.

Get Free Alerts โ†’ Free ยท No credit card ยท 60 sec setup

CVSS v3 Breakdown

CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L
Attack Vector
Attack Complexity
Privileges Required
User Interaction
Scope
Confidentiality
Integrity
Availability

Affected Versions

Siemens / Desigo DXR2
0 < V01.21.233.16-7862
Siemens / Desigo PXC3
0 < V01.21.233.16-7862
Siemens / Desigo PXC4
0 < V02.21.194.36-2715
Siemens / Desigo PXC5.E003
0 < V02.21.194.36-2715
Siemens / Desigo PXC5.E24
0 < V02.21.194.36-2715
Siemens / Desigo PXC7
0 < V02.21.194.36-2715

References

NVD โ†— CVE.org โ†— EPSS Data โ†—
cert-portal.siemens.com: https://cert-portal.siemens.com/productcert/html/ssa-781903.html