CVE-2026-124760
Alarm receiver stops delivering alarms after a malformed alarm notification
CVSS Score
0.0
EPSS Score
0.0%
EPSS Percentile
0th
P-Net before 1.0.4 sets the alarm receiver state to waiting for confirmation before the data of a received alarm notification is parsed. If the parsing fails the state is not restored, and later alarm notifications of the same priority are discarded without acknowledge until the Application Relationship is released. The Application Relationship and the cyclic data exchange keep working. The attacker must be able to send an alarm notification in the context of an established Application Relationship and requires ADJACENT network access.
| CWE | CWE-754 |
| Vendor | rt-labs |
| Product | p-net |
| Published | Nov 13, 2026 |
Stay Ahead of the Next One
Get instant alerts for rt-labs p-net
Be the first to know when new unknown vulnerabilities affecting rt-labs p-net are published โ delivered to Slack, Telegram or Discord.
Get Free Alerts โ
Free ยท No credit card ยท 60 sec setup
Affected Versions
RT-Labs / P-Net
0 < 1.0.4
References
Credits
Aditya Gupta (Attify - attify.com)